Battery Capacity Formula:
From: | To: |
The Fire Panel Battery Calculator determines the minimum required battery capacity (in ampere-hours) for a fire alarm system based on standby and alarm current draw. Proper battery sizing ensures the system remains operational during power outages.
The calculator uses the following formula:
Where:
Explanation: The calculation accounts for 24 hours of standby operation plus 30 minutes of alarm operation, with an additional 25% safety margin.
Details: Correct battery capacity ensures fire alarm systems remain operational during power failures, meeting NFPA 72 requirements for emergency operation duration.
Tips: Measure standby current with all devices in normal state and alarm current with all notification appliances activated. Enter values in amps (decimal values accepted).
Q1: Why is there a 1.25 multiplier?
A: The 25% safety margin accounts for battery aging, temperature effects, and manufacturing tolerances.
Q2: What if my system has different duration requirements?
A: Adjust the 24 and 0.5 hour values in the formula to match your local regulations or specific requirements.
Q3: Should I round up the battery size?
A: Yes, always select the next standard battery size above the calculated value.
Q4: Does this account for battery temperature effects?
A: No, for cold environments (below 20°C/68°F), additional capacity may be needed.
Q5: How often should batteries be tested?
A: NFPA 72 recommends annual full-duration testing under load to verify capacity.