Battery Capacity Equation:
From: | To: |
The battery capacity calculation determines the required battery size for fire alarm systems according to NFPA 72 standards. It accounts for both standby and alarm current draws over a 24-hour period with a 25% safety factor.
The calculator uses the following equation:
Where:
Explanation: The equation calculates total energy requirements for 24 hours of standby plus 5 minutes of alarm, then adds a 25% safety margin.
Details: Proper battery sizing ensures fire alarm systems remain operational during power outages for code-required durations (typically 24 hours standby plus 5 minutes alarm).
Tips: Enter standby current (normal operating current) and alarm current (current during alarm condition) in amps. Both values must be zero or positive.
Q1: Why is there a 25% safety factor?
A: The 1.25 multiplier accounts for battery aging, temperature effects, and provides a margin of safety as required by NFPA 72.
Q2: What's the 0.083 hour factor?
A: This represents 5 minutes (0.083 hours) which is the NFPA requirement for alarm duration during power failure.
Q3: How do I measure standby and alarm currents?
A: Standby current is measured with system in normal operation. Alarm current is measured with all alarm devices activated.
Q4: Does this calculation work for all fire alarm systems?
A: This is for standard systems. Special systems (voice evacuation, etc.) may require additional calculations.
Q5: What battery type should I use?
A: Sealed lead-acid batteries are most common, but consult manufacturer specifications for your specific fire alarm control panel.