UPS Battery Equation:
From: | To: |
The UPS Battery Calculator determines the required battery capacity (in ampere-hours) needed to power a UPS load for a specified duration. It's essential for proper UPS system design and ensuring adequate backup power.
The calculator uses the battery capacity equation:
Where:
Explanation: The equation calculates how much current (in amperes) the battery needs to supply for how many hours to meet the power requirement.
Details: Proper battery sizing ensures your UPS system can support the connected load for the required duration during power outages, preventing equipment downtime.
Tips: Enter the total UPS load in watts, desired backup time in hours, and battery bank voltage (typically 12V, 24V, or 48V). All values must be positive numbers.
Q1: Should I add a safety margin to the calculated Ah?
A: Yes, it's recommended to add 20-30% to account for battery aging, temperature effects, and conversion losses.
Q2: What's the difference between Ah and Wh?
A: Ah (ampere-hours) measures charge capacity, while Wh (watt-hours) measures energy capacity. Wh = Ah × V.
Q3: How does battery voltage affect capacity?
A: Higher voltage systems require fewer Ah for the same power, but may need more batteries in series.
Q4: What's typical backup time for UPS systems?
A: Common backup times range from 5-30 minutes for small UPS to several hours for large installations.
Q5: Does battery type affect the calculation?
A: The basic calculation works for all types, but lead-acid batteries typically shouldn't be discharged below 50% capacity for long life.