Fire Alarm Battery Formula:
From: | To: |
The Fire Alarm Battery Calculation Formula determines the minimum required battery capacity (in amp-hours) to power a fire alarm system for 24 hours in standby plus 30 minutes in alarm mode, with a 25% safety margin.
The calculator uses the following equation:
Where:
Explanation: The formula calculates the total amp-hours needed for 24 hours standby plus 30 minutes alarm, then adds 25% capacity for safety margin and battery aging.
Details: Proper battery sizing is critical for fire alarm system reliability. Undersized batteries may fail to maintain operation during power outages, while oversized batteries increase cost and space requirements unnecessarily.
Tips: Enter the standby current (typically provided in the fire alarm panel specifications) and the alarm current (sum of all notification appliances during alarm). Both values must be in amps.
Q1: Why is there a 25% safety margin?
A: The margin accounts for battery aging, temperature effects, and manufacturing variations to ensure reliable operation throughout the battery's service life.
Q2: What are typical standby and alarm currents?
A: Standby current is usually 0.1-0.5A for small systems. Alarm current depends on connected devices (horns, strobes) but can be 1-5A or more.
Q3: Does this meet code requirements?
A: This calculation meets NFPA 72 requirements for 24 hours standby plus 5 minutes alarm (30 minutes is commonly used for extra safety).
Q4: Should I round up the battery size?
A: Yes, always round up to the next standard battery size available (e.g., 7.2Ah → 7Ah or 9Ah depending on options).
Q5: How often should batteries be replaced?
A: Typically every 3-5 years, or when capacity drops below 80% of rated capacity.