Battery Capacity Formula:
From: | To: |
Fire alarm battery capacity calculation determines the minimum battery size required to power a fire alarm system during both standby and alarm conditions, with appropriate safety margins.
The calculator uses the standard formula:
Where:
Explanation: The formula calculates total energy requirement for both standby and alarm modes, then applies a safety factor to account for battery aging and temperature effects.
Details: Correct battery sizing ensures fire alarm systems remain operational during power outages and can sound alarms when needed. Undersized batteries may fail prematurely, while oversized batteries are unnecessarily costly.
Tips: Enter standby current (normal operation current), alarm current (current during alarm activation), and derating factor (typically 1.2). All values must be positive numbers.
Q1: What is the 24-hour requirement based on?
A: NFPA 72 requires fire alarm systems to operate for 24 hours in standby plus 5 minutes in alarm during power outages.
Q2: Why use a derating factor of 1.2?
A: The 20% margin accounts for battery aging, temperature effects, and manufacturing variations.
Q3: Should I round up the calculated capacity?
A: Yes, always select the next standard battery size above the calculated value.
Q4: Does this apply to all battery types?
A: The calculation works for lead-acid batteries. Lithium batteries may have different derating factors.
Q5: How often should batteries be tested?
A: NFPA 72 recommends monthly visual inspections and annual load testing.