Battery Capacity Formula:
From: | To: |
The fire alarm panel battery calculation determines the minimum battery capacity required to power a fire alarm system during standby and alarm conditions for 24 hours plus 5 minutes of alarm time, with a 25% safety factor.
The calculator uses the following equation:
Where:
Explanation: The equation calculates total energy requirements for 24 hours of standby plus 5 minutes of alarm, then adds a 25% safety margin.
Details: Proper battery sizing is critical for fire alarm system reliability. Undersized batteries may fail during power outages, while oversized batteries increase cost and space requirements unnecessarily.
Tips: Enter the panel's standby current (typically found in technical specifications) and maximum alarm current (including all connected devices). Both values must be in Amps.
Q1: Why is there a 25% safety factor?
A: The safety factor accounts for battery aging, temperature effects, and manufacturing variations to ensure reliable operation throughout the battery's service life.
Q2: What if my system has different standby requirements?
A: Some jurisdictions may require longer standby times (e.g., 60 or 120 hours). Adjust the "24" in the formula to match your local requirements.
Q3: Should I use measured or rated current values?
A: For most accurate results, use measured values. If unavailable, use manufacturer's rated maximum values.
Q4: Does this account for battery efficiency?
A: The calculation assumes typical lead-acid battery performance. For other battery types (e.g., lithium), consult manufacturer specifications.
Q5: How often should batteries be replaced?
A: NFPA 72 recommends replacement every 3-5 years, or when capacity drops below 80% of rated capacity.