Firelite Battery Equation:
From: | To: |
The Firelite battery calculation determines the required battery capacity (in ampere-hours) for Firelite fire alarm control panels based on standby current and alarm current draw.
The calculator uses the Firelite battery equation:
Where:
Explanation: The equation calculates total energy needed for 24 hours of standby plus 5 minutes of alarm, then adds a 25% safety margin.
Details: Proper battery sizing ensures the fire alarm system remains operational during power outages for code-required durations while maintaining sufficient capacity for alarm operation.
Tips: Enter standby current and alarm current in amps. Values must be positive numbers. Typical values range from 0.1A to several amps depending on system size.
Q1: Why is there a 1.25 multiplier?
A: The 1.25 multiplier (25% additional capacity) accounts for battery aging, temperature effects, and provides a safety margin.
Q2: What battery types are suitable?
A: Sealed lead-acid (SLA) batteries are typically used, sized to meet or exceed the calculated capacity.
Q3: How often should batteries be replaced?
A: NFPA recommends replacement every 3-5 years or when capacity drops below 80% of rated capacity.
Q4: Does this calculation meet code requirements?
A: This follows NFPA 72 requirements for 24 hours standby plus 5 minutes alarm, but always verify local codes.
Q5: What if my system has multiple alarm currents?
A: Use the highest alarm current draw expected during full system activation.